ANALISIS PENANGANAN GANGGUAN VOLTAGE UNBALANCE DI MOTOR INDUKSI 3 PHASA PADA PANEL MOTOR CONTROL CENTER MENGGUNAKAN PFR DI PT. SEMESTA ELTRINDO PURA

Wicaksono, Mochammad Arif (2015) ANALISIS PENANGANAN GANGGUAN VOLTAGE UNBALANCE DI MOTOR INDUKSI 3 PHASA PADA PANEL MOTOR CONTROL CENTER MENGGUNAKAN PFR DI PT. SEMESTA ELTRINDO PURA. Diploma thesis, POLITEKNIK PERKAPALAN NEGERI SURABAYA.

Full text not available from this repository.

Abstract

ABSTRAK Gangguan voltage unbalance sangatlah mengganggu pada proses produksi, karena gangguan voltage unbalance berdampak besar pada motor induksi 3 phasa yang merupakan jenis motor paling sering digunakan pada proses produksi di industri. Voltage Unbalance menyebabkan ke tidak seimbangan arus yang mengalir menuju belitan stator motor. Gangguan tersebut mempunyai dampak yang sangat berbahaya pada motor, bila dibiarkan berlarut-larut akan mengakibatkan peningkatan suhu dan dapat mengakibatkan motor induksi 3 phasa terbakar dikarenakan arus yang mengalir sangat besar. Penggunaan PFR (Phase Failure Relay) merupakan solusi yang cepat, fleksibel, dan efisien untuk mengatasi masalah gangguan voltage unbalance. PFR berfungsi untuk menjaga tegangan altenator agar tetap konstan, maka altenator akan tetap mengeluarkan tegangan yang selalu konstan pada harga nominalnya dalam keadaan beban yang berubah-ubah dan diusahakan selalu berputar pada kecepatan nominalnya. Penggunaan Thermal Overload juga dapat digunakan, namun tidaklah semaksimal PFR dalam cara kerjanya, karena hanya mendeteksi tegangan lebih saja. Sehingga Thermal Overload bukanlah alat proteksi yang utama. Dengan menggunakan metode analisa data yang diperoleh dari perusahaan masalah penanganan gangguan voltage unbalance yang terjadi pada motor induksi 3 phasa bisa dilakukan dengan hasil : pada bulan ke-1 sampai bulan ke-4 dan bulan ke-6 besar tegangannya relatif stabil mendekati angka nominalnya 380V, dengan besar tegangan antar phasanya pada bulan ke-1 (364V, 357V, 371V) dan arus nominal tiap phasanya (15,66A, 16,2A, 15,8A). Pada bulan ke-5 besar tegangan antar phasa jauh mendekati angka nominalnya (264 V, 283V, 375V) dengan besar arus (0,4A, 17,7A, 40A), lalu terjadilah gangguan unbalance voltage dengan besar tegangan antar phasa. %Unbalance Voltage sebesar 12,06% (Standart perusahaan sebesar 10%) untuk pencegahan terjadinya voltage unbalance dilakukan dengan cara memasang alat proteksi berupa Phase Failure Relay (PFR) pada supply tegangan masuk. Kata kunci : Voltage Unbalance, Motor induksi 3 phasa, PFR, Thermal overload, Motrol Control Center ABSTRACT Voltage unbalanced disturbance does disturb in the process of production because it has impact on the 3 phase of motor induction that is the most frequent type of motor used in the production process in industry. Voltage unbalanced will cause a flow unbalanced towards the bend of motor stator. That disturbance has risky impact for motor if it is kept constantly because it could be an extremely huge flow that will increase the temperature and cause 3 phasa of motor induction burned down. PFR (Phase Failure Relay) using is a quick, flexible, and efficient solution to solve the voltage unbalanced disturbance. PFR serves to keep alternator voltage constant, then alternator will put outside the constant voltage persistently at nominal cost always in the alternating load condition and sought always spin at nominal speed. Thermal overload could solve however but it is not as maximal as PFR in the way of its working because it detects surge voltage only. So, Thermal overload is not a main protection tool. By using the method of analysis of data obtained from the company handling problems interruption of voltage unbalance which occurs in induction motors 3-phase can be done with the results: in the 1st until the 4th and the 6th month a large voltage is relatively stable approaching nominal 380V, with its phase of the voltage between the months-1 (364V, 357V, 371V) and its nominal current of each phase (15,66A, 16,2A, 15,8A). In the 5th phase of the voltage across much honing nominal (264 V, 283V, 375V) with a current (0,4A, 17,7A, 40A), and there was a great disturbance to the voltage unbalance between phase voltages. % Voltage unbalance by 12.06% (Standart company by 10%) for the prevention of voltage unbalance is done by placing a protective device in the form of Phase Failure Relay (PFR) in supply Key Words : Voltage Unbalance, Motor induksi 3 phasa, PFR, Thermal Overload, Motrol Control Center.

Item Type: Thesis (Diploma)
Subjects: T Technology > T Technology (General)
Divisions: Jurusan Teknik Kelistrikan Kapal > D3 Teknik Kelistrikan Kapal
Depositing User: Unnamed user with email repository@ppns.ac.id
Date Deposited: 30 Aug 2018 02:12
Last Modified: 30 Aug 2018 02:12
URI: http://repository.ppns.ac.id/id/eprint/251

Actions (login required)

View Item View Item