Perancangan hidran dengan menggunakan software pipe flow expert dan evaluasi APAR (alat pemadam api ringan) pada PT. X

DESIGN OF HYDRANTS BY USING THE PIPE FLOW EXPERT SOFTWARE AND APAR (ALAT PEMADAM API RINGAN) EVALUATION AT PT. X

Pungky Ardi Kumara (6510040049)


Abstrak

PT. X merupakan perusahaan manufaktur fabrikasi dengan produk seperti; Shell and Tube, coloum, beam, tangki dan lain-lain. Dalam proses produksi terdapat proses pengelasan dan pemotongan plat dengan menggunakan Liquid Petrolium Gas (LPG) yang berpotensi menyebabkan kebakaran atau peledakan. Berdasarkan risk assessment , PT. X mempunyai potensi bahaya kebakaran cukup tinggi. Namun PT. X belum mempunyai alat pemadam kebakaran yang cukup memadai, karena disana hanya terdapat Alat Pemadam Api Ringan (APAR) yang jumlahnya tidak sesuai dengan ketentuan dan juga belum tersedia instalasi sistem hidran sebagai alat pemadam kebakaran. Intalasi sistem hindran mengacu pada NFPA 14-2003 untuk menetukan standar sistem pipa tegak dan selang dan SNI 03-1745-2000 untuk menentukan tata cara perencanaan dan pemasangan sistem pipa tegak dan selang untuk pencegahan bahaya kebakaran pada bangunan rumah dan gedung. Sedangkan alat pemadam api ringan yang digunakan mengacu pada NFPA 10 tahun 2002 untuk menetukan standar APAR dan Permenakertrans RI No.PER-04/MEN/1980 untuk Syarat-Syarat pemasangan dan pemeliharaan APAR. Dari hasil perhitungan jumlah pilar hidran yang dibutuhkan untuk proteksi kebakaran di PT. X sebanyak 4 buah hidran pada workshop 1, 2 dan 3 serta 5 buah hidran pada workshop 4. Perhitungan headloss menggunakan software Pipe Flow Expert didapatkan nilai headloss total sebesar 5,213153 m, sedangkan dari perhitungan manual didapatkan nilai headloss total sebesar 5,67538004 m. Untuk daya pompa yang dibutuhkan sesuai dengan perhitungan headloss software Pipe Flow Expert sebesar 2,87046835 HP dengan besar water power 2,152851 HP. Sedangkan berdasarkan perhitungan headloss secara manual, daya pompa yang dibutuhkan sebesar 3,09313098 HP dengan water power 2,319848 HP. Untuk perhitungan APAR Berdasarkan Permenaker No. 04/Men/1980 dibutuhkan penambahan sebanyak 32 buah APAR Sedangkan berdasarkan standart NFPA 10 tahun 2002, dibutuhkan penambahan sebanyak 12 buah APAR dan jenis APAR yang paling cocok untuk semua ruangan di PT.X yaitu Dry Chemical. Kata kunci: APAR, Daya pompa, Instalasi sistem hidran.


Abstract

PT. X is a fabrication manufacturing company with products such as: Shell and Tube, column, beam, tank and others. In production process, there are plate welding and cutting processes by using Liquefied Petroleum Gas (LPG) with the potential to cause the fire or explosion hazard. Based on risk assessment, PT. X has the high enough fire hazard potential. But, PT. X has not had the sufficient fire extinguisher, due to only Light Fire Extinguishers (Alat Pemadam Api Ringan [APAR]) there, whose amount do not appropriate with the stipulation and there also not yet available hydrant system as the fire extinguisher. Hydrant system installation refer to NFPA 14-2003 to determine the standard system of upright pipe and hose and SNI 03-1745-2000 to determine the designing and fixing methods of upright pipe and hose for fire hazard prevention on house and building. While, the light extinguisher used was referred to NFPA 10 of 2002 to determine the APAR standard and the Permenakertrans RI No. PER-04/MEN/1980 for the APAR fixing and maintenance requirements. From the calculation result of hydrant pillar amounts needed for fire protection at PT. X as many as 4 hydrants in workshop 1, 2 and 3 and 5 hydrants in workshop 4. From the headloss calculation used Pipe Flow Expert software it was obtained total headloss values of 5,213153 m, while from manual calculation it was obtained total headloss of 5,67538004 m. For the pump power needed was agree with the headloss calculation of Pipe Flow Expert software of 2,87046835 HP with water power of 2,152851 HP. For the pump power needed was agree with the headloss calculation of manual of 3,09313098 HP with water power of 2,319848 HP. For the APAR calculation based on the Permenaker No. 04/Men/1980 it was needed addition of 32 APARs. While, based on the standard of NFPA 10 of 2002, it was needed addition of 12 APARs and the most suitable APAR type for all spaces in PT. X was Dry Chemical. Key words: APAR, Hydrant system installation, Pump power.


Detil Peneliti

Dosen Pembimbing 1 :Eko Julianto
Dosen Pembimbing 2 : Moch Luqman Ashari

Program Studi : D4 - TEKNIK KESELAMATAN DAN KESEHATAN KERJA
Angkatan : 2010