ANALISIS PROTEKSI UNDERVOLTAGE PADA SISTEM TEGANGAN MENENGAH DI PT. ALP PETRO INDUSTRY

ANALYSIS UNDERVOLTAGE PROTECTION IN MEDIUM VOLTAGE SYSTEM AT PT. ALP PETRO INDUSTRY

Achmad Romandhoni (6410030035)


Abstrak

ABSTRAK Jaringan tegangan menengah memiliki beberapa sistem proteksi diantaranya yaitu sistem proteksi undervoltage. Sistem proteksi undervoltage pada jaringan tegangan menengah merupakan sistem yang digunakan oleh PT. ALP Petro Industry. PT. ALP Petro Industry merupakan industri pembuat oli mesin yang berlokasi di daerah gempol, Pasuruan. Sistem proteksi ini sangat diperlukan untuk mencegah terjadinya kerusakan pada peralatan yang menggunakan tenaga listrik. Metode yang dipakai dalam Tugas Akhir ini yaitu membandingkan sistem proteksi undervoltage yang terpasang dengan standar setting relai menurut aturan PUIL serta perhitungan yang semestinya. Berdasarkan pembahasan Tugas Akhir ini, setting relai tegangan kurang tidak sesuai dengan standar PUIL. Karena setting relai tegangan kurang disetting 70% dari tegangan nominal selama 2 detik, sedangkan menurut aturan PUIL untuk setting relai tegangan kurang disetting minimum 80% dari tegangan nominal selama 3 detik. Kondisi peralatan saat tegangan turun membuat putaran motor menjadi rendah sehingga kerja motor tidak akan maksimal yang dapat menyebabkan kegagalan produksi. . Kata kunci : Distribusi tegangan menengah, proteksi undervoltage, jaringan tegangan menengah, setting relai.


Abstract

ABSTRACT Medium voltage network has several protection systems among which the under voltage protection system. Under voltage protection system at the medium voltage network is a system used by PT. ALP Petro Industry. PT. ALP Petro Industry is an industrial manufacturer that the engine oil is located in gempol, Pasuruan. The protection system is necessary to prevent damage to the equipment that uses electricity. The method used in the final project was to compare the under voltage protection system installed according to standard rules of relay settings and calculations should PUIL. Based on this final discussion, not less voltage relay settings according to the standard PUIL. Because the relay setting voltage is less setting 70% of nominal voltage for 2 seconds, while according to the rules for setting relays PUIL less voltage be set a minimum of 80% of nominal voltage for 3 seconds. Equipment condition when the voltage drops to make the motor to be low so that the motor will not work up that could lead to failure of production. Keywords: Distribution medium voltage, under voltage protection, medium voltage network, setting relays.


Detil Peneliti

Dosen Pembimbing 1 :Achmad Syahid
Dosen Pembimbing 2 : Achmad Syahid

Program Studi : D3 - TEKNIK KELISTRIKAN KAPAL
Angkatan : 2010


Untuk mendapatkan versi full dari dokumen penelitian ini, Anda dapat melihat koleksi Buku Tugas Akhir di Perpustakaan Politeknik Perkapalan Negeri Surabaya pada jam kerja. Atau Anda dapat menghubungi penulis secara personal.